Industrial Products
Explore HANS industrial products engineered for precision, reliability, and demanding applications. Filter by product system, type, technology, bond type, or grit to find the right solution for your requirements.
Products

ET56 Wireless Temperature Acquisition Unit
Industrial IoT
Wireless Temperature Acquisition Unit
Technology · Bond Type · Grit
GRIT / MESH
BOND TYPE
TECHNOLOGY
SPECIFICATIONS
ET56
Model: ET56
Specification: ET56
Measurement range: 433 MHz wireless; ≤60 m in open area
Power supply: DC 5 V (external adapter)
Communication: RS-485 Modbus RTU; 433 MHz wireless reception
Operating temperature: −20 to +65°C
Installation: DIN-rail mounting

ET70 Bus Wireless Temperature Data Acquisition Unit
Industrial IoT
Bus Wireless Temperature Data Acquisition Unit
Technology · Bond Type · Grit
GRIT / MESH
BOND TYPE
TECHNOLOGY
SPECIFICATIONS
ET70
Model: ET70
Specification: HANS-ET70 Bus Wireless Temperature Data Acquisition Unit
Power supply: AC85–265V or DC120–370V
Communication: One or two RS485 Modbus RTU interfaces; one or two 433MHz LoRa receiving antennas optional
Operating temperature: −20 to +70°C
Operating humidity: 5–95%RH non-condensing

ETB05
Industrial IoT
Electrical Equipment Temperature Sensor
Technology · Bond Type · Grit
GRIT / MESH
BOND TYPE
TECHNOLOGY
SPECIFICATIONS
ETB05
Model: HANS-ETB05 V1.2 strap-type active pipe surface temperature sensor.
Measurement: Pipeline surface temperature range 0–180°C; accuracy ±1°C.
Wireless: 433 MHz; open-environment wireless distance ≤150 m; transmission power 10 dB; data rate 5000 bps.
Power: 3.6 V lithium battery, 1200 mAh; stated battery life greater than 2 years under the source's operating conditions.
Sampling and reporting: Sampling period 30 seconds; upload interval 10 seconds; when temperature changes by more than 0.5°C, upload immediately; 60-day data history.
Physical: Strap length 390 mm; sensor body 36 × 36 × 27 mm; silicone rubber housing; waterproof and dustproof construction.

ETC05
Industrial IoT
Electrical Equipment Temperature Sensor
Technology · Bond Type · Grit
GRIT / MESH
BOND TYPE
TECHNOLOGY
SPECIFICATIONS
ETC05
Model: ETC05
Specification: HANS-ETC05 Passive CT-Powered Temperature Sensor
Measurement range: Temperature 0–180°C
Accuracy: ±1°C
Power supply: CT energy harvesting; starting primary current ≥3A; no battery rating stated
Communication: 433MHz wireless, ≤150m unobstructed

ETC06
Industrial IoT
Temperature Sensor
Technology · Bond Type · Grit
GRIT / MESH
BOND TYPE
TECHNOLOGY
SPECIFICATIONS
ETC06
Model: ETC06
Specification: ETC06 Online-Powered Wireless Temperature Sensor
Measurement range: 0–180 °C
Power supply: Online-powered; startup current >5 A
Communication: 433 MHz wireless

EWG Electronic Water Level Gauge
Industrial IoT
Electronic Water Level Gauge
Technology · Bond Type · Grit
GRIT / MESH
BOND TYPE
TECHNOLOGY
SPECIFICATIONS
EWG-RS485
Model: EWG-RS485
Specification: EWG Electronic Water Level Gauge — RS-485
Measurement range: Per section: 80 cm or 50 cm; sections can be combined
Power supply: DC 9–30 V
Communication: RS-485; Modbus RTU
EWG-4G
Model: EWG-4G
Specification: EWG Electronic Water Level Gauge — 4G
Measurement range: Per section: 80 cm or 50 cm; sections can be combined
Power supply: DC 9–30 V
Communication: 4G Cat.1; TCP/IP

FG01 Household Combustible Gas Detector
Industrial IoT
Combustible Gas Detector
Technology · Bond Type · Grit
GRIT / MESH
BOND TYPE
TECHNOLOGY
SPECIFICATIONS
FG01
Model: HANS-FG01 V1.0 household combustible gas detector for methane/natural gas only. The manual explicitly states it is not suitable for detecting other gases.
Detection/alarm: Semiconductor gas sensor; alarm threshold 8%LEL; response <30s; audible alarm 70–115dB with visual alarm; historical event storage: 200 alarm records, 200 alarm-recovery records, 100 fault records, 100 fault-recovery records, 50 power-off and 50 power-on records.
Electrical: AC220V/50Hz; power ≤3W. Alarm outputs are alternatives: one DC12V active pulse output for solenoid valve, and one optional passive dry-contact output for fan control. The device section says choose one of the two output modes; do not claim both are present on every unit.
Environment/life: Indoor household use; 0 to +55°C; 10–95% RH non-condensing; service life ≥5 years in clean air; wall mount; 125 × 75 × 36mm.
Operation: Initial warm-up approximately 180s; alarm recovery when combustible gas concentration falls below the set threshold; self-test by short press; long press silences; sensor fault and end-of-life indications. Network state can be uploaded wirelessly; manual shows connectivity but no specific wireless protocol or model-specific communication register map.
Installation: For methane, mount on ceiling or within 0.3m below ceiling, preferably within 1.5m of gas source, in same room and same separated area as gas appliance. Avoid direct heat from stove, oil fumes, bathrooms/high humidity, aerosols, paint, adhesives and other irritating vapors.
Safety boundary: Natural gas/methane only. Do not infer LPG, propane, CO or other gas detection. Valve pulse and fan relay are selectable output configurations.

FPTD-34 High-Spatial-Resolution Distributed Fiber Optic Temperature Monitoring Host
Industrial IoT
Distributed Fiber Optic Temperature Monitoring Host
Technology · Bond Type · Grit
GRIT / MESH
BOND TYPE
TECHNOLOGY
SPECIFICATIONS
FPTD-34
Model: FPTD-34
Specification: FPTD-34 Distributed Fiber Optic Temperature Monitoring Host
Measurement range: −200 to 800 °C (actual monitoring capability depends on selected fiber)
Accuracy: 3 km: ±0.5 °C; 6 km: ±1 °C; 12 km: ±1 °C
Resolution: Temperature 0.1 °C; spatial 0.2/0.4/0.8 m at 3/6/12 km
Power supply: AC 220 V, 0.5 A, 50 Hz
Communication: Wired Ethernet; MODBUS; OTAP
Operating temperature: −15 to 55 °C

FS01
Industrial IoT
Weather Sensor
Technology · Bond Type · Grit
GRIT / MESH
BOND TYPE
TECHNOLOGY
SPECIFICATIONS
FS01
Model: HANS-FS01 V1.1 cup-type wind-speed sensor (manual cover prints V1.0 beneath the model; version record p.2396 records V1.1 and notes contact-details update).
Measurement: Wind-speed ranges 0–30m/s, 0–50m/s or 0–60m/s; other ranges customizable. Starting wind speed ≤0.3m/s. Accuracy ±(0.3 + 0.03V)m/s. Stabilization time <1s; response time <1s. Reports wind speed and Beaufort wind-force level.
Supply/output configurations: DC 5–24V for 0–2V or RS485 outputs; DC 12–24V for 0–5V, 0–10V or 4–20mA. Output options: one of 0–2V/0–5V/0–10V, 4–20mA current loop, or RS485 Modbus RTU. Analog version uses 3-wire cable; RS485 uses 4-wire cable; 2m standard cable, length selectable. Do not assume multiple output types are simultaneously installed.
Environment/construction: Operating temperature -30 to +70°C; working humidity ≤100% RH; storage temperature -30 to +70°C; storage humidity ≤100% RH. Cup anemometer housing is aluminum, weather-resistant, high-strength, corrosion-resistant and waterproof.
Communications: RS485 Modbus RTU; address 1–252, default 1; baud 1200/2400/4800/9600/57600/115200, default 9600; 8 data bits, no parity, 1 stop bit, CRC. Register 0x0000 returns wind speed and wind-force level; register address can be changed using function 0x06. Wind-speed register value is divided by 10 to obtain m/s; wind-force value is an integer.
Analog conversion: For 0–30m/s: 0–2V, speed=15×V; 0–5V, speed=6×V; 0–10V, speed=3×V; 4–20mA, speed=1.875×A−7.5. For 0–60m/s: 0–2V, speed=30×V; 0–5V, speed=12×V; 0–10V, speed=6×V; 4–20mA, speed=3.75×A−15. Pulse conversion listed as 0.083m/s per pulse.
Installation/use: The sensor is a precision instrument; do not disassemble or alter factory wiring/components. Avoid moisture and sticky particles entering the sensor. For RS485, observe A/B polarity, baud, address and polling timing; the manual recommends poll/wait intervals above 200ms.
Configuration boundary: Select one range and one output/supply combination for the ordered unit. Other ranges and cable lengths are customizable.

FS02
Industrial IoT
Weather Sensor
Technology · Bond Type · Grit
GRIT / MESH
BOND TYPE
TECHNOLOGY
SPECIFICATIONS
FS02
Model: HANS-FS02 V1.0 duct air-velocity sensor for ventilation and exhaust ducts.
Measurement: Selectable ranges 0–5, 0–10, 0–15, 0–20 or 0–30m/s; resolution 0.1m/s; accuracy ±(0.2m/s + 2%FS); response <1s; long-term stability ≤0.1m/s/year. Maximum calculated airflow 0–65.535m³/s; configurable duct cross-section 0–6.5535m².
Electrical/output: DC12–24V; current 55mA@12V and 25mA@24V. Output types listed: 0–5V, 4–20mA or RS485. The conversion table also includes 0–2V formulas, although 0–2V is not listed in the main output-type table; retain this discrepancy pending confirmation. Analog conversion formulas are supplied for 0–5/10/20/30m/s ranges; no formula is supplied for the 15m/s option.
Environment: Operating -30 to +70°C; storage -40 to +80°C. Current-loop load limits depend on supply: <250Ω at 9V, <400Ω at 12V, <500Ω at 20V, <900Ω at 24V.
Installation: Duct probe insertion with flange mounting and silicone sealing. Install on duct side or underside; do not install from top down. Align flow-direction marking with airflow direction.
Communications: RS485 Modbus RTU, default address 01, 9600bps, no parity, 8 data bits, 1 stop bit. Address write uses function 0x06 at register 0x0030; data query uses 0x03. Registers report wind speed, wind-force level and calculated airflow. Duct cross-section is stored at register 0x003F and can be written/read; example uses scale 0.0001m² per count.
Configuration boundary: Select the range and output variant for the ordered unit. Keep the 0–2V conversion-table reference and the missing 15m/s conversion formula as source discrepancies; do not invent either.

FSA01 Standalone Smoke Alarm
Industrial IoT
Smoke Detector
Technology · Bond Type · Grit
GRIT / MESH
BOND TYPE
TECHNOLOGY
SPECIFICATIONS
FSA01
Model: HANS-FSA01 standalone smoke alarm. Designed for occupied locations to detect smoke generated by fire and provide audible fire warning; built-in buzzer.
Electrical and alarm: DC 9 V 6F22 battery; standby current ≤15 μA; alarm current ≤18 mA; sound pressure ≥80 dB at 3 m.
Radio: 433 MHz RF band.
Environment: Working temperature -10 to +55°C; relative humidity ≤95%, non-condensing. ABS housing; weight 120 g including battery; diameter 105.0 mm; height 56.5 mm including base; mounting-hole spacing 62.5 mm.
Use limitation: Intended for occupied locations. Not suitable for persistent residual smoke, heavy dust, water mist, steam, oil mist, corrosive gas, relative humidity above 95%, or ventilation speed above 5 m/s.

FX01
Industrial IoT
Weather Sensor
Technology · Bond Type · Grit
GRIT / MESH
BOND TYPE
TECHNOLOGY
SPECIFICATIONS
FX01
Model: HANS-FX01 V1.1 wind-direction sensor.
Measurement: Direction 0–360°; accuracy ±1°; resolution 0.1°; starting wind speed ≤0.5m/s; maximum rotation radius 100mm.
Supply/output variants: DC5–24V for 0–2V or RS485; DC12–24V for 0–5V, 0–10V or 4–20mA. Select one output: 0–2V, 0–5V, 0–10V, 4–20mA or RS485 Modbus RTU. Analog output and RS485 wiring/output configurations are alternatives.
Environment/protection: Operating temperature -30 to +70°C; humidity ≤100% RH; IP65. Aluminum housing with weather-resistant, corrosion-resistant and waterproof construction.
Communications: RS485 Modbus RTU; 8 data bits, no parity, 1 stop bit, CRC; baud 1200/2400/4800/9600/57600/115200bps, default 9600; device address default 1. Read registers return wind direction angle and 16-point compass direction; angle is raw value divided by 10, direction code 0x00–0x0F.
Direction mapping: The manual provides 16 sectors: N, NNE, NE, ENE, E, ESE, SE, SSE, S, SSW, SW, WSW, W, WNW, NW and NNW, with analog voltage/current thresholds and RS485 codes.
Configuration boundary: Output type and matching supply voltage must be selected together. Do not transfer FS01 wind-speed measurement values to FX01.
- Page 18