TE0 Duct Temperature & Humidity Sensor
Industrial IoT
Duct Temperature & Humidity Sensor
Technology · Bond Type · Grit
GRIT / MESH
BOND TYPE
TECHNOLOGY
SPECIFICATIONS
TE0
Model: HANS-TE0 V1.3 duct temperature and humidity sensor.
Measurement: Standard temperature ranges -30 to +70°C or 0 to +50°C; other ranges customizable. Humidity 0–100% RH, non-condensing. Accuracy ±0.2°C at 25°C and ±3% RH from 10–90% RH. Repeatability ±0.1°C and ±0.1% RH. Long-term stability <0.04°C/year and <0.5% RH/year.
Electrical/output variants: Selectable 0–2V, 0–5V, 0–10V, 4–20mA, RS485 Modbus RTU or SDI-12. Supply 5–24VDC for 0–2V/RS485/SDI-12; 12–24VDC for 0–5V/0–10V/4–20mA. Power ≤0.3W; response <1s. Operating environment -55 to +120°C and humidity <100% RH.
Analog scaling (for -30…+70°C configuration): 0–2V: temperature=50×V−30, humidity=50×V. 0–5V: temperature=20×V−30, humidity=20×V. 0–10V: temperature=10×V−30, humidity=10×V. 4–20mA: temperature=6.25×A−55, humidity=6.25×A−25.
RS485 communications: Modbus RTU, default address 01, 9600bps, no parity, 8 data bits, 1 stop bit. Function 0x06 changes address; function 0x03 reads temperature and humidity. Data registers include temperature, humidity, dew point and wet-bulb temperature, with integer tenths and floating-point representations.
Installation: Duct mounting on the side or underside only; do not install from top down. Use the flange to adjust insertion depth. Keep away from chemical corrosion, high-voltage sources and heat sources.
Configuration boundary: Output type and corresponding supply voltage must be selected together. Standard temperature measurement ranges differ from the analog scaling example (-30…+70°C); preserve both. RS485, SDI-12 and analog are separate output options.

TEMT-04 Automatic Underground Termite Monitoring Device
Industrial IoT
Termite Monitoring Device
Technology · Bond Type · Grit
GRIT / MESH
BOND TYPE
TECHNOLOGY
SPECIFICATIONS
Technical Overview
TEMT-04 is an automatic termite monitoring device using non-loop electromagnetic induction technology. technical documentations document both Cat.1/4G and LoRa variants, automatic intrusion alarm/location reporting, IP68 sealed construction and battery operating life of at least three years.
Scope: concise source-supported product summary. Consult the exact model/version manual for complete configuration, electrical and communication details.

TEMT-VI-4G Visual Underground Termite Monitoring Device
Industrial IoT
Visual Termite Monitoring Device
Technology · Bond Type · Grit
GRIT / MESH
BOND TYPE
TECHNOLOGY
SPECIFICATIONS
Technical Overview
TEMT-VI-4G is a visual underground termite monitoring device combining non-loop electromagnetic induction, HD camera image verification and remote treatment control. The technical documentation describes Cat.1/4G image return, AI-assisted visual verification, remote spray control and IP68 sealing.
Scope: concise source-supported product summary. Consult the exact model/version manual for complete configuration, electrical and communication details.

TEMT-WG01 Outdoor LoRa IoT Gateway
Industrial IoT
Outdoor LoRa IoT Gateway
Technology · Bond Type · Grit
GRIT / MESH
BOND TYPE
TECHNOLOGY
SPECIFICATIONS
Technical Overview
TEMT-WG01 is an outdoor LoRa IoT gateway using a Semtech SX1302 eight-channel transceiver in half-duplex mode. The technical documentation specifies LoRa self-organizing networking, 4G and 10/100M Ethernet backhaul, optional GNSS, IP68 enclosure and optional photovoltaic/PoE power.
Scope: concise source-supported product summary. Consult the exact model/version manual for complete configuration, electrical and communication details.

TRWSNPO21
Industrial IoT
Soil Sensor
Technology · Bond Type · Grit
GRIT / MESH
BOND TYPE
TECHNOLOGY
SPECIFICATIONS
TRWSNPO21
Model: TRWSNPO21
Specification: HANS-TRWSNPO21 8-Parameter Soil Sensor
Measurement range: Soil temperature −40 to +80°C; moisture 0–100% VWC; EC 0–20000μS/cm; salinity 0–20000mg/L; N/P/K 0–1999mg/kg (or mg/L); pH 3–10
Accuracy: Temperature ±0.3°C; moisture ±2%; EC ±3%; salinity ±3%; N/P/K ±3%; pH ±0.2
Resolution: Temperature 0.1°C; moisture 0.1%; EC 1μS/cm; salinity 1mg/L; N/P/K 1mg/kg or mg/L; pH 0.01
Power supply: 5–24V DC
Communication: RS-485 Modbus RTU
Installation: Insert probes fully into soil or bury the sensor body; sensing region approx. 7cm diameter × 7cm height

TSM4-4G-L Multi-Layer Soil Moisture Monitoring Station
Industrial IoT
Multi-Layer Soil Moisture Monitoring Station
Technology · Bond Type · Grit
GRIT / MESH
BOND TYPE
TECHNOLOGY
SPECIFICATIONS
TSM4-4G-L
Measurement: Soil temperature and volumetric soil moisture. Temperature range -40 to 80°C; moisture range 0–100% (m³/m³). Accuracy: temperature ±0.3°C; moisture ±2%. Resolution: temperature 0.1°C; moisture 0.1% (m³/m³).
Construction: Product weight 1.2 kg (3 layers; each additional layer adds approximately 0.3 kg); 304 stainless-steel enclosure; 316L stainless-steel probe; probe length 56 mm and diameter 3 mm; epoxy seal; IP68.
Electrical: Working current 20 mA; 9–24 V isolated supply (1500 VDC isolation voltage); RS485 isolated output (1414 VDC isolation supply); Modbus RTU.
Station configuration: 4G communications; solar supply 30 W + 12 V 17 Ah; 25 × 47 mm; 3–8 layers, total length 400–900 mm; operating temperature -40 to 80°C; 2 m cable, extendable on request.

TSM4-8P-4G-L
Industrial IoT
Multi-Layer Soil Moisture Monitoring Station
Technology · Bond Type · Grit
GRIT / MESH
BOND TYPE
TECHNOLOGY
SPECIFICATIONS
TSM4-8P-4G-L
Eight-parameter station: Soil temperature, volumetric moisture, EC, salinity, nitrogen, phosphorus, potassium and pH.
Ranges: Temperature -40 to 80°C; moisture 0–100% (m³/m³); EC 0–20000 μS/cm; salinity 0–20000 mg/L; N/P/K 0–1999 mg/kg (mg/L); pH 3–10.
Accuracy: Temperature ±0.3°C; moisture ±2%; EC ±3%; salinity ±3%; N/P/K ±3%; pH ±0.2. Resolution: 0.1°C; 0.1% (m³/m³); 1 μS/cm; 1 mg/L; 1 mg/kg (mg/L); pH 0.01.
Construction and electrical: 304 stainless-steel enclosure; 316L stainless steel, aluminum and zinc probe materials; probe length 56 mm, diameter 3 mm; epoxy seal; IP68; working current 20 mA; 9–24 V isolated supply (1500 VDC isolation voltage); RS485 isolated output (1414 VDC isolation supply); Modbus RTU.
Station configuration: 4G communications; solar supply 30 W + 12 V 17 Ah; 25 × 47 mm; 3–8 layers, total length 400–900 mm; operating temperature -40 to 80°C; 2 m cable, extendable on request.

ULG01 Ultrasonic Level Meter
Industrial IoT
Ultrasonic Level Meter
Technology · Bond Type · Grit
GRIT / MESH
BOND TYPE
TECHNOLOGY
SPECIFICATIONS
ULG01
Model: ULG01
Specification: HANS-ULG01 Ultrasonic Level Meter
Measurement range: Standard 5, 10, 15, 20 m; optional 1, 30, 40, 50, 60 m
Accuracy: 0.5–1.0% under actual field measurement
Resolution: 3 mm or 0.1%, whichever is greater
Power supply: 6 V DC low-power variant; 12 V DC; 24 V DC; 220 VAC depending on configuration
Communication: RS-485; RS-232 optional
Output signal: 4–20 mA; optional relay; RS-485; RS-232 optional
Installation: Probe/thread/flange installation; exact mounting and range depend on integrated/split configuration

ULM01 Integrated Ultrasonic Level Meter
Industrial IoT
Integrated Ultrasonic Level Meter
Technology · Bond Type · Grit
GRIT / MESH
BOND TYPE
TECHNOLOGY
SPECIFICATIONS
ULM01
Model: ULM01
Specification: HANS-ULM01 Integrated Ultrasonic Level Meter
Measurement range: Integrated ultrasonic level meter: selectable 5, 10, 15, 20, 30, 40, 50, or 60m
Accuracy: 0.5–1.0%
Resolution: 3mm or 0.1% of range, whichever is greater
Power supply: Integrated model standard DC24V; optional AC220V 50Hz. Separate type has different defaults.
Communication: Optional RS485 or RS232 (device-specific serial protocol)
Operating temperature: Display −20 to +60°C; probe −20 to +80°C

ULM02 Split Ultrasonic Level Meter
Industrial IoT
Split Ultrasonic Level Meter
Technology · Bond Type · Grit
GRIT / MESH
BOND TYPE
TECHNOLOGY
SPECIFICATIONS
HANS-ULM02
Measurement: Range options 5, 10, 15, 20, 30, 40, 50, 60 or 70 m; accuracy 0.5%–1.0%; resolution 3 mm or 0.1%, whichever is greater. Distance or level measurement modes; configurable 4–20 mA mapping.
Display and probe: LCD display; display operating temperature −20 to +60°C; probe −20 to +80°C; display IP65 and probe IP68. Probe cable up to 100 m; 10 m standard.
Electrical and outputs: Standard supply 220 VAC +15%, 50 Hz; optional 24 VDC; custom 12 VDC or battery supply. 4–20 mA output, 510 Ω load. Optional programmable relays: single-channel two sets or dual-channel four sets; AC 250 V/8 A or DC 30 V/5 A.
Communications: Optional RS485 or RS232 using the device-specific serial protocol. Address default 1; baud rates 2400/4800/9600/19200, default 9600. Do not assume Modbus compatibility without confirmation.
Installation: Keep the probe axis perpendicular to the measured surface; avoid obstructions and false echoes from pipes, supports, welds and internal structures. Installation conditions, blind zone and probe selection affect measurement performance. Keep sensor wiring separated from AC/power cables and apply appropriate shielding and grounding.
Configuration: Relay count, supply, communication interface and probe range are configuration-dependent.

UWSD03 Ultrasonic Wind Speed & Direction Sensor
Industrial IoT
Ultrasonic Wind Sensor
Technology · Bond Type · Grit
GRIT / MESH
BOND TYPE
TECHNOLOGY
SPECIFICATIONS
UWSD03
Model: HANS-UWSD03 V1.1 ultrasonic wind speed and direction sensor.
Wind speed: 0–60 m/s; resolution 0.01 m/s; accuracy ±(0.3 + 0.03v) m/s at ≤30 m/s and ±(0.3 + 0.05v) m/s at ≥30 m/s. Wind direction: 0–360°; resolution 0.1°; accuracy ±3° when wind speed is below 10 m/s.
Output and power: RS-485 Modbus RTU; DC 12–24 V or solar option; operating current <30 mA; heater average current <3 A only if heater is fitted.
Construction and environment: ASA engineering plastic; IP65; dimensions 251 × 182 × 182 mm; fixed sleeve mounting; flange support options 1.5 m and 3 m. Optional GPS and display publication options are separately listed.
Configuration boundary: The manual also describes a separate 4–20 mA output variant in the wiring section. It is not merged into the standard RS-485 configuration as a simultaneous output.

UWSD05 Ultrasonic Wind Speed & Direction Meter
Industrial IoT
Ultrasonic Wind Sensor
Technology · Bond Type · Grit
GRIT / MESH
BOND TYPE
TECHNOLOGY
SPECIFICATIONS
UWSD05
Model: HANS-UWSD05 V1.0 ultrasonic wind speed and direction meter.
Wind speed: 0–40 m/s; accuracy ±(0.5 + 0.05V) m/s; resolution 0.01 m/s; sampling 10 Hz. Wind direction: 0–360°; accuracy ±5° when wind speed is below 10 m/s; resolution 0.1°; sampling 10 Hz.
Output and power: Standard RS-485 Modbus RTU; optional SDI-12 module; DC 9–24 V. Maximum output frequency: passive mode 1/s; active mode 1/min.
Environment and installation: Operating temperature -30 to 70°C; IP65; standard sleeve fixing; optional adapter and 1.5 m / 1.8 m brackets; 3 m standard cable, optional 10 m cable.
Separation: Do not transfer UWSD03's 0–60 m/s range, solar option or heater-current values to UWSD05.

VMG301-S1 4G Wireless Three-Axis Vibration & Temperature Sensor
Industrial IoT
Vibration / Condition Monitoring Sensor
Technology · Bond Type · Grit
GRIT / MESH
BOND TYPE
TECHNOLOGY
SPECIFICATIONS
VMG301-S1
Wireless 4G three-axis sensor: X/Y/Z vibration axes; vibration velocity range 0–200 mm/s; accuracy ±2% at 80 Hz and 10 mm/s; resolution 0.1 mm/s. Temperature accuracy ±1°C at 25°C ambient; measurement range -40 to 85°C, or -40 to 165°C with extension rod; resolution 0.1°C.
Communications: 4G wireless; MQTT reporting by default; configurable TCP custom HEX reporting. Uploaded data includes XYZ vibration velocity, temperature, battery level, signal strength, report interval, alarm settings, timestamp, ICCID and version.
Power and environment: 3.6 V lithium thionyl chloride battery, 8.5 Ah; sleep current less than 12 μA; IP67; working temperature -40 to 85°C; working humidity 0–90% RH; mine-safety type.
Configuration: Sampling interval options 1, 5, 10, 15, 30 or 60 minutes (default 60); upload options 1, 5, 10, 15, 30, 60, 120, 240, 360, 720 or 1440 minutes (default 60). Battery life >3 years at default 60-minute sampling and upload. Installation dimensions Ø43 mm × 100 mm (90 mm housing + 10 mm stud or magnet); M8 × 10 thread; magnetic, threaded or magnet-plus-adhesive installation.

VML301-S1 LoRa Wireless Three-Axis Vibration & Temperature Sensor
Industrial IoT
Vibration / Condition Monitoring Sensor
Technology · Bond Type · Grit
GRIT / MESH
BOND TYPE
TECHNOLOGY
SPECIFICATIONS
VML301-S1
LoRa wireless three-axis sensor: X/Y/Z vibration axes; velocity range 0–200 mm/s; accuracy ±5% at 80 Hz and 10 mm/s; velocity resolution 0.1 mm/s. Frequency range 10–1600 Hz; frequency resolution 1 Hz. Temperature accuracy ±0.5°C; range -40 to 85°C; resolution 0.1°C.
Power and environment: 3.6 V lithium thionyl chloride battery, 8.5 Ah; sleep current less than 12 μA; IP67; working temperature -40 to 85°C; working humidity 0–90% RH; mine-safety type. Dimensions Ø40 mm × 80 mm; M8 × 10 thread.
Sampling and battery life (p.1608): Sampling options 1, 5, 10, 15, 30 or 60 minutes (default 60); upload options 1, 5, 10, 15, 30, 60, 120, 240, 360, 720 or 1440 minutes (default 60). Battery-life table: 5-minute sampling / 60-minute upload: 0.8 years; 60/60: 1 year; 10/120: 1.5 years; 30/240: greater than 3 years. The same page separately states that transmitting data every 5 minutes gives approximately 1 year; it does not specify the sampling interval for that statement, so retain it as a separate manufacturer FAQ note rather than merging it with the table row.
Network: One acquisition unit supports 40 nodes. Device default logic is 1-minute sampling and 5-minute upload; a vibration-velocity change greater than 0.2 mm/s between two samples triggers immediate upload.

WPSR-RPS 24GHz Radar Parking Space Detector
Industrial IoT
Radar Parking Space Detector
Technology · Bond Type · Grit
GRIT / MESH
BOND TYPE
TECHNOLOGY
SPECIFICATIONS
WPSR-RPS
Model: HANS-WPSR-RPS, 24 GHz radar parking-space detector, V1.0.
Detection: 24 GHz FMCW radar; configurable detection distance 1–5 m; maximum detection-distance error ±0.3 m; manufacturer-stated vehicle detection accuracy ≥99.9%; response time ≤3 s; horizontal angle ±7.5°, pitch angle ±30°; programmable FMCW.
Communications and power: POWERBUS power/communication two-wire bus; Bluetooth 5.0; DC 12–48 V; average current 66 mA at 12 V; maximum operating current 85 mA at 12 V; average power 0.8 W at 12 V.
Construction and environment: ABS/PC enclosure; IP65; operating temperature -35 to +65°C; net weight 136 g; gross weight 187 g; device size 107.7 × 99.3 × 63.7 mm excluding fixing screw; single package 115 × 115 × 115 mm.
Indicators and commissioning: Seven indicator colors (red, blue, green, purple, cyan, yellow, white), adjustable brightness 1–100%; Bluetooth commissioning; near-end and remote OTA; fault self-check and low-voltage alarm; basic self-calibration after activation.
Application: Indoor and semi-outdoor parking spaces including hospitals, hotels, scenic areas, shopping centers, office-building underground garages and parking structures.

WPSR-WG POWERBUS Parking Detector Gateway
Industrial IoT
Parking Detector Gateway
Technology · Bond Type · Grit
GRIT / MESH
BOND TYPE
TECHNOLOGY
SPECIFICATIONS
WPSR-WG
WPSR-WG parking detector gateway: POWERBUS two-wire bus integrating power and communication; Ethernet; RS485 reserved; three RJ45 Ethernet switch ports; Bluetooth configuration; network/app configuration; near-end and remote OTA support.
Capacity and power: Supports up to 200 parking detector nodes; built-in 350 W switching power supply; AC 180–264 V / 50 Hz input; maximum operating current 2 A.
Construction and environment: Cold-rolled steel enclosure; working temperature -35 to 65°C; device dimensions 337 × 273.5 × 89.3 mm; net weight 3.5 kg; gross weight 3.8 kg; package dimensions 370 × 310 × (130 ±20) mm.

XFKA1 Multi-Function Level Display and Alarm Control Box
Industrial IoT
Multi-Function Level Display and Alarm Control Box
Technology · Bond Type · Grit
GRIT / MESH
BOND TYPE
TECHNOLOGY
SPECIFICATIONS
XFKA1
HANS-XFKA1: multi-function level display and alarm control box for 4–20mA process input, display, control and buzzer alarm.
Power options: AC 220V, AC 380V or AC/DC 24V; actual supplied variant must be confirmed. Power consumption: ≤6W.
Measurement/display: Class 0.2 accuracy; 250Ω input impedance. Optional outputs: 4–20mA retransmission, RS485 Modbus RTU, up to four relays; do not assume all options are included.
Relay: 250V/5A. Analog output load: 1000Ω. Auxiliary power: DC24V/40mA. Communication baud: 2400–115200bps, default 9600.
Environment: -10 to +60°C, ≤85% RH. Original source: HANS-XFKA1 manual, 组合1 pp.2249–2262. Page-heading variant XFK01 remains a documented source printing discrepancy. Configuration and availability subject to quotation.

XFKA2 Multi-Function Process Display & Alarm Controller
Industrial IoT
Process Display & Alarm Controller
Technology · Bond Type · Grit
GRIT / MESH
BOND TYPE
TECHNOLOGY
SPECIFICATIONS
XFKA2
Model: HANS-XFKA2, V1.1, multi-function process display and alarm controller. The cover at p.2263 and product overview at p.2266 identify XFKA2. The running header/contents label XFK02 on pp.2265 and 2269–2276 is retained as an editorial printing error; it is not a separate model.
Power: AC 220V, AC 380V or AC/DC 24V. Power consumption ≤6W.
Input/display: Standard 4–20mA input; configurable display range -1999 to 9999 with freely configurable decimal point. Bar-graph resolution 5%, display ratio configurable.
Outputs: Default no output unless specified before factory delivery; optional 4–20mA retransmission and RS485; up to four relay outputs. Accuracy class 0.2. Input impedance 250Ω; analog output load capacity 1000Ω; relay load 250V/5A; auxiliary supply DC24V/40mA with automatic overcurrent protection.
Communications: RS485 Modbus RTU. Baud rate 2400–115200bps, configurable, default 9600bps. Slave address 1–254, default 1; address 0 is broadcast and does not receive a reply. Read holding registers function 03H; write single register function 06H; CRC16 polynomial A001h. Register table includes display/input values, display scaling, alarm thresholds/hysteresis, address and baud rate. Parameter values with decimals are transmitted as signed 16-bit integers with the decimal point scaled (e.g. 1.000 transmitted as 1000).
Environment: Operating temperature -10 to +60°C; relative humidity ≤85% RH.
Configuration boundary: Output options are factory-order options and must be confirmed for the delivered configuration. Do not assume all optional outputs are installed on every unit. This XFKA2 record remains inactive pending specification QA.

XFKA3 Multi-Function Process Display & Alarm Controller
Industrial IoT
Process Display & Alarm Controller
Technology · Bond Type · Grit
GRIT / MESH
BOND TYPE
TECHNOLOGY
SPECIFICATIONS
XFKA3
Model: HANS-XFKA3, V1.1, multi-function process display and alarm controller. The cover at p.2277 and product overview at p.2280 identify XFKA3. The running header/contents label XFK03 on pp.2279 and 2285–2290 is retained as an editorial printing error; it is not a separate model.
Power: AC 220V, AC 380V or AC/DC 24V. Power consumption ≤6W.
Input/display: Standard 4–20mA input; configurable display range -1999 to 9999 with freely configurable decimal point. Bar-graph resolution 5%, display ratio configurable.
Outputs: Default no output unless specified before factory delivery; optional 4–20mA retransmission and RS485; up to four relay outputs. Accuracy class 0.2. Input impedance 250Ω; analog output load capacity 1000Ω; relay load 250V/5A; auxiliary supply DC24V/40mA with automatic overcurrent protection.
Communications: RS485 Modbus RTU. Baud rate 2400–115200bps, configurable, default 9600bps. Slave address 1–254, default 1; address 0 is broadcast and does not receive a reply. Read holding registers function 03H; write single register function 06H; CRC16 polynomial A001h. Register table includes display/input values, display scaling, alarm thresholds/hysteresis, address and baud rate. Parameter values with decimals are transmitted as signed 16-bit integers with decimal point scaled (e.g. 1.000 transmitted as 1000).
Environment: Operating temperature -10 to +60°C; relative humidity ≤85% RH.
Configuration boundary: Output options are factory-order options and must be confirmed for the delivered configuration. Do not assume all optional outputs are installed on every unit. This XFKA3 record remains inactive pending specification QA.

HANS-Z3TDV6-06 PoE Three-Axis Vibration and Temperature Sensor
Industrial IoT
Vibration / Condition Monitoring Sensor
Technology · Bond Type · Grit
GRIT / MESH
BOND TYPE
TECHNOLOGY
SPECIFICATIONS
Measurement and electrical specifications
- Axes: X, Y, Z, synchronous measurement.
- Velocity: 0–200 mm/s; accuracy ±1.5%; resolution 0.1 mm/s.
- Acceleration: ±16 g; accuracy ±1.5%; resolution 0.01 g.
- Displacement: 0–5000 μm; accuracy ±3%; resolution 1 μm.
- Vibration accuracy reference: 80 Hz, 10 mm/s.
- Frequency: 10–6000 Hz; accuracy ±1.5%; resolution 1 Hz.
- Housing temperature: −40 to +85°C; accuracy ±0.5°C; resolution 0.1°C.
- Power: PoE, maximum 3 W. Ethernet connection to a PoE switch; confirm connector and PoE standard before installation.
- Operating environment: −40 to +85°C; 0–95% RH, non-condensing.
- IP67 stainless-steel housing; Ø26 × 111 mm; nut across flats 27 mm.
- Mounting: M8 × 1.25 mm threaded mounting or magnetic base.
Firmware selection
B: temperature, velocity, acceleration, displacement and frequency. C: B plus spectrum. D: B plus 15 statistical features. E: B plus spectrum and 15 statistical features. Confirm firmware and waveform availability when ordering; these options are not separate confirmed SKUs.
Network and configuration
Ethernet; Modbus TCP or MQTT with JSON payloads, selectable. Static IP or DHCP; configurable gateway, DNS, reporting interval, 10 or 20 kHz sampling, MQTT server, port, credentials and topic. PC configuration utility supports device discovery, parameter configuration and firmware updates. In MQTT mode use device capture for configuration and release capture afterward to resume cloud reporting.
Waveform and protocol
Modbus TCP functions 0x03 and 0x06. Waveform acquisition uses 2000 acceleration samples per axis: 10 kHz/200 ms or 20 kHz/100 ms. Modbus uses 16 packets of 125 samples per axis; JSON example uses 10 packets of 200 samples per axis at 20 kHz. Sample unit 0.001 g, signed int16; JSON example is big-endian. Confirm statistical feature units for the selected interface.
Alarm configuration
Alarm modes: 0 disabled, 1 outside range, 2 inside range, 3 below low threshold, 4 above high threshold, 5 change-difference. Alarm flags: temperature 8, Z 4, Y 2, X 1. Velocity threshold units 0.1 mm/s; temperature threshold units 0.1°C.
Installation and applications
Mount close to the bearing housing on a flat, rigid surface. Prefer threaded mounting for high vibration and long-term critical equipment monitoring. Route Ethernet away from high-power drive cables. Suitable for condition monitoring of motors, fans, pumps, compressors and gearboxes. Hazardous-area deployment requires separately confirmed certification.