TE0 Duct Temperature & Humidity Sensor
TE0 is a duct temperature and humidity sensor with analog, RS485 Modbus RTU or SDI-12 output options. Source specifications provide -30–70°C standard temperature range, 0–100%RH and fast response.


PRODUCT TYPE
Duct Temperature & Humidity Sensor
TECHNOLOGY
TECHNICAL DATA
Model: HANS-TE0 V1.3 duct temperature and humidity sensor.
Measurement: Standard temperature ranges -30 to +70°C or 0 to +50°C; other ranges customizable. Humidity 0–100% RH, non-condensing. Accuracy ±0.2°C at 25°C and ±3% RH from 10–90% RH. Repeatability ±0.1°C and ±0.1% RH. Long-term stability <0.04°C/year and <0.5% RH/year.
Electrical/output variants: Selectable 0–2V, 0–5V, 0–10V, 4–20mA, RS485 Modbus RTU or SDI-12. Supply 5–24VDC for 0–2V/RS485/SDI-12; 12–24VDC for 0–5V/0–10V/4–20mA. Power ≤0.3W; response <1s. Operating environment -55 to +120°C and humidity <100% RH.
Analog scaling (for -30…+70°C configuration): 0–2V: temperature=50×V−30, humidity=50×V. 0–5V: temperature=20×V−30, humidity=20×V. 0–10V: temperature=10×V−30, humidity=10×V. 4–20mA: temperature=6.25×A−55, humidity=6.25×A−25.
RS485 communications: Modbus RTU, default address 01, 9600bps, no parity, 8 data bits, 1 stop bit. Function 0x06 changes address; function 0x03 reads temperature and humidity. Data registers include temperature, humidity, dew point and wet-bulb temperature, with integer tenths and floating-point representations.
Installation: Duct mounting on the side or underside only; do not install from top down. Use the flange to adjust insertion depth. Keep away from chemical corrosion, high-voltage sources and heat sources.
Configuration boundary: Output type and corresponding supply voltage must be selected together. Standard temperature measurement ranges differ from the analog scaling example (-30…+70°C); preserve both. RS485, SDI-12 and analog are separate output options.
SPECIFICATIONS
TE0
Model: HANS-TE0 V1.3 duct temperature and humidity sensor.
Measurement: Standard temperature ranges -30 to +70°C or 0 to +50°C; other ranges customizable. Humidity 0–100% RH, non-condensing. Accuracy ±0.2°C at 25°C and ±3% RH from 10–90% RH. Repeatability ±0.1°C and ±0.1% RH. Long-term stability <0.04°C/year and <0.5% RH/year.
Electrical/output variants: Selectable 0–2V, 0–5V, 0–10V, 4–20mA, RS485 Modbus RTU or SDI-12. Supply 5–24VDC for 0–2V/RS485/SDI-12; 12–24VDC for 0–5V/0–10V/4–20mA. Power ≤0.3W; response <1s. Operating environment -55 to +120°C and humidity <100% RH.
Analog scaling (for -30…+70°C configuration): 0–2V: temperature=50×V−30, humidity=50×V. 0–5V: temperature=20×V−30, humidity=20×V. 0–10V: temperature=10×V−30, humidity=10×V. 4–20mA: temperature=6.25×A−55, humidity=6.25×A−25.
RS485 communications: Modbus RTU, default address 01, 9600bps, no parity, 8 data bits, 1 stop bit. Function 0x06 changes address; function 0x03 reads temperature and humidity. Data registers include temperature, humidity, dew point and wet-bulb temperature, with integer tenths and floating-point representations.
Installation: Duct mounting on the side or underside only; do not install from top down. Use the flange to adjust insertion depth. Keep away from chemical corrosion, high-voltage sources and heat sources.
Configuration boundary: Output type and corresponding supply voltage must be selected together. Standard temperature measurement ranges differ from the analog scaling example (-30…+70°C); preserve both. RS485, SDI-12 and analog are separate output options.