HANS-SP11 Smart Differential Pressure Transmitter
The HANS-SP11 is a wired smart differential pressure transmitter for industrial process monitoring. The manufacturer describes an imported single-crystal-silicon diffused-silicon sensing element, an LCD backlit display and adjustable range, zero and damping settings. Published measuring ranges span 100 Pa to 3 MPa with customization; accuracy grades are offered as 0.075%, 0.1%, 0.2% or 0.5%. Output configurations are selectable and include 4–20 mA, 4–20 mA with RS485 Modbus, or 4–20 mA with HART. The manufacturer lists 12–24 V DC supply, IP65 protection, 16 MPa static-pressure design, and process-media temperature from −40 to +105°C. Confirm the exact calibrated range, accuracy grade, output, pressure connection, wetted materials and any hazardous-area certification on the order-specific datasheet before selection.


PRODUCT TYPE
Differential Pressure Transmitter
TECHNOLOGY
TECHNICAL DATA
SPECIFICATIONS
HANS-SP11 Smart Differential Pressure Transmitter
Measurement range: 100 Pa–3 MPa, customizable. Accuracy grades offered: 0.075%, 0.1%, 0.2% and 0.5%.
Stability and drift: manufacturer-stated long-term stability ≤0.02% FS/year and temperature drift ≤0.02% FS/°C. Verify these values against the selected range and order-specific datasheet.
Electrical: 12–24 V DC. Selectable output versions: 4–20 mA; 4–20 mA + RS485 Modbus; or 4–20 mA + HART. These are alternative configurations, not simultaneous standard outputs.
Process: media listed as liquids, gases and steam; process-media temperature −40 to +105°C. Ambient temperature −20 to +70°C. IP65. Manufacturer-stated static-pressure design 16 MPa.
Connections: NPT 1/4 standard; NPT 1/2 and M20 × 1.5 customizable. Optional two-valve and three-valve manifolds.
Display and adjustment: backlit LCD; range, zero and damping adjustment.
Hazardous areas: product page describes an explosion-proof housing structure, but no certificate number, protection marking, issuing authority or standard was supplied. Do not treat this description as verified hazardous-area certification.
KEY FEATURES
- Imported single-crystal-silicon diffused-silicon sensing element, as stated by the manufacturer.
- Selectable accuracy grades: 0.075%, 0.1%, 0.2% or 0.5%.
- Published range 100 Pa–3 MPa, customizable; confirm the selected calibrated range.
- Backlit LCD local display; field adjustment of range, zero and damping.
- Selectable 4–20 mA, 4–20 mA + RS485 Modbus, or 4–20 mA + HART output versions.
- IP65 enclosure; manufacturer states 16 MPa static-pressure design.
- Optional two-valve or three-valve manifold.
PRODUCT SYSTEM