LDG-W05 Five-in-One Partial Discharge Sensor

The HANS-LDG-W05 is a battery-powered multi-parameter partial discharge sensor for online condition monitoring of high-voltage electrical equipment. It combines acoustic emission (AE), transient earth voltage (TEV), ultra-high-frequency (UHF) sensing, environmental temperature and humidity, and background noise monitoring. Discharge measurements and PRPS/PRPD pattern data are transmitted over a 433 MHz wireless link to the HANS-LDG-G20 monitoring host for edge processing and diagnostic analysis.

Industrial IoT OEM and ODM engineering for custom sensors, wireless devices and IoT gateways
LDG-W05 — Reference illustration from product documentation. Verify the exact model, variant, interface and mechanical configuration against the original manufacturer manual before ordering.

PRODUCT TYPE

Partial Discharge Monitoring Sensor

TECHNOLOGY

Acoustic emission; transient earth voltage; ultra-high-frequency partial discharge sensing

TECHNICAL DATA

AE: 0–60 dBµV, 37–43 kHz. TEV: 0–60 dBmV, 3–100 MHz. UHF: −45 to +10 dBm, 300–1500 MHz. Noise: 40–120 dB. Temperature measurement: −40 to +125°C, ±1°C; humidity measurement: 0–100% RH, ±3% RH. Default sampling 30 min and reporting 10 min, separately configurable; confirm timing behavior for the intended monitoring strategy. 433 MHz wireless, up to 200 m in open areas. Lithium thionyl chloride battery, nominal three-year life; actual life depends on operation. Outputs include background noise, discharge amplitude, pulse count, warning level and PRPS/PRPD data. Compatible host: HANS-LDG-G20. Sensor body dimensions, ambient operating limits, battery capacity and IP rating not confirmed.

External equipment mounting, wireless pairing and host-side configuration by authorized personnel in accordance with site electrical safety procedures. No unconditional live-work authorization implied.

SPECIFICATIONS

AE: 0–60 dBµV, 37–43 kHz. TEV: 0–60 dBmV, 3–100 MHz. UHF: −45 to +10 dBm, 300–1500 MHz. Noise: 40–120 dB. Temperature measurement: −40 to +125°C, ±1°C; humidity measurement: 0–100% RH, ±3% RH. Default sampling 30 min and reporting 10 min, separately configurable; confirm timing behavior for the intended monitoring strategy. 433 MHz wireless, up to 200 m in open areas. Lithium thionyl chloride battery, nominal three-year life; actual life depends on operation. Outputs include background noise, discharge amplitude, pulse count, warning level and PRPS/PRPD data. Compatible host: HANS-LDG-G20. Sensor body dimensions, ambient operating limits, battery capacity and IP rating not confirmed.

External equipment mounting, wireless pairing and host-side configuration by authorized personnel in accordance with site electrical safety procedures. No unconditional live-work authorization implied.

KEY FEATURES

  • AE, TEV and UHF partial discharge detection
  • Temperature, humidity and background noise monitoring
  • PRPS and PRPD discharge pattern data
  • 433 MHz wireless link to HANS-LDG-G20
  • Battery-powered operation and configurable sampling and reporting