L5301 Intelligent Wireless Acquisition Terminal
L5301 is an intelligent wireless acquisition terminal for temperature, temperature/humidity, vibration, water-leak, door-contact, smoke, SF6+O2 and partial-discharge sensors. The technical documentation specifies downstream LoRa and upstream RS232, RS485 Modbus RTU and Ethernet Modbus TCP, with optional 4G, Wi-Fi and 5G expansion.


PRODUCT TYPE
Data Acquisition Unit
TECHNOLOGY
TECHNICAL DATA
Identity and role (组合1 p.3891–3894): HANS-L5301 V1.4 Intelligent Wireless Data Acquisition Terminal. Collects data from temperature, temperature/humidity, vibration, water-leak, door-contact, smoke, SF6+O2 and partial-discharge sensors.
Technical table (p.3894): Ambient temperature -40 to +85°C; ambient humidity 0–90% RH; working voltage 12–36 VDC; downlink LoRa; uplink RS-232, RS-485 and Ethernet; optional 4G, Wi-Fi and 5G expansion; LoRa line-of-sight range 3000 m; enclosure 100 × 72 × 25 mm; fixed mounting with mounting holes; stated service life >10 years.
Sensor configuration capacity (p.3898): Single-value sensor entries up to 120; dual-value up to 240; three-value up to 60; four-value up to 60. Device offline timeout is configurable in hours, minimum 1 hour, default 24 hours.
Value mapping (p.3901): V1–V4 fields vary by sensor type; three-axis vibration maps X/Y/Z; three-axis vibration plus temperature maps X/Y/Z and temperature.
Communications (p.3902): UART and RS485 use Modbus RTU at 9600 bps, 8 data bits, 1 stop bit, no parity. RJ45 uses Modbus TCP; default IP 192.168.1.111, subnet 255.255.255.0, gateway 192.168.1.1, port 1200 (configurable).
Register map (pp.3902–3904): Includes device serial number, Modbus ID, Ethernet configuration, single-value sensor block at 0x0400, dual-value block at 0x0800 (SF6+O2), three-value block at 0x1000, four-value block at 0x4000, and upload counter at 0x8300. Function 0x03 reads sensor values; 0x04 reads registers/configuration/IDs; 0x10 writes registers.
Power-supply variance: The p.3894 technical table specifies 12–36 VDC. The p.3904 usage notes state DC9–40 V may be used in field conditions, while also specifying a DC12V adapter as standard. Preserve both statements; do not normalize the power field until the manufacturer confirms their relationship.
SPECIFICATIONS
L5301
Identity and role (组合1 p.3891–3894): HANS-L5301 V1.4 Intelligent Wireless Data Acquisition Terminal. Collects data from temperature, temperature/humidity, vibration, water-leak, door-contact, smoke, SF6+O2 and partial-discharge sensors.
Technical table (p.3894): Ambient temperature -40 to +85°C; ambient humidity 0–90% RH; working voltage 12–36 VDC; downlink LoRa; uplink RS-232, RS-485 and Ethernet; optional 4G, Wi-Fi and 5G expansion; LoRa line-of-sight range 3000 m; enclosure 100 × 72 × 25 mm; fixed mounting with mounting holes; stated service life >10 years.
Sensor configuration capacity (p.3898): Single-value sensor entries up to 120; dual-value up to 240; three-value up to 60; four-value up to 60. Device offline timeout is configurable in hours, minimum 1 hour, default 24 hours.
Value mapping (p.3901): V1–V4 fields vary by sensor type; three-axis vibration maps X/Y/Z; three-axis vibration plus temperature maps X/Y/Z and temperature.
Communications (p.3902): UART and RS485 use Modbus RTU at 9600 bps, 8 data bits, 1 stop bit, no parity. RJ45 uses Modbus TCP; default IP 192.168.1.111, subnet 255.255.255.0, gateway 192.168.1.1, port 1200 (configurable).
Register map (pp.3902–3904): Includes device serial number, Modbus ID, Ethernet configuration, single-value sensor block at 0x0400, dual-value block at 0x0800 (SF6+O2), three-value block at 0x1000, four-value block at 0x4000, and upload counter at 0x8300. Function 0x03 reads sensor values; 0x04 reads registers/configuration/IDs; 0x10 writes registers.
Power-supply variance: The p.3894 technical table specifies 12–36 VDC. The p.3904 usage notes state DC9–40 V may be used in field conditions, while also specifying a DC12V adapter as standard. Preserve both statements; do not normalize the power field until the manufacturer confirms their relationship.
KEY FEATURES
L5301 is an intelligent wireless acquisition terminal for temperature, temperature/humidity, vibration, water-leak, door-contact, smoke, SF6+O2 and partial-discharge sensors. The technical documentation specifies downstream LoRa and upstream RS232, RS485 Modbus RTU and Ethernet Modbus TCP, with optional 4G, Wi-Fi and 5G expansion.